What an RCD does and how to test it each month
Last updated
Quick answer: An RCD (often labelled RCCB) is the safety switch in your home's distribution board that cuts the power if current leaks. Suruhanjaya Tenaga's safety booklet says to test it at least once a month. Press its test button. If it trips, it works. If it does not trip, call a registered electrical contractor.
Free for homeowners. Dispatcher does not do the work.
Get quotesOn this page
What an RCD is, in plain words
An RCD is a switch that watches for current leaking out of your wiring, for example through a faulty appliance or a person. When it senses a leak, it cuts the supply. Suruhanjaya Tenaga (ST), Malaysia's energy regulator, calls it a device that protects you from electric shock (ST, "Tip Keselamatan dan Kecekapan Tenaga").
RCD stands for residual current device. In Malay it is the Peranti Arus Baki, or PAB. On many boards it carries the label RCCB, which is one type of RCD. The other type named in ST's rules is the RCBO, which adds overcurrent protection in the same unit.
ST's domestic wiring guideline sets three rules for the RCD in your board (ST, "Garis Panduan Pendawaian Elektrik Pepasangan Domestik"):
- An RCCB or RCBO must be a type approved by ST, with the ST-SIRIM label.
- It must work on current. The older voltage-operated ELCB is not allowed.
- An RCD must be rated for at least as much current as the nearest breaker that feeds it.
You do not have to check these yourself. They are worth knowing if a contractor offers to swap the unit.
The monthly test, from the official booklet
ST's safety booklet says to test the RCD at least once a month, so you know it can cut the circuit when current leaks. A working RCD trips, and the power cuts out at once (ST, "Tip Keselamatan dan Kecekapan Tenaga").
The test uses the button on the front of the RCD. ST's domestic guideline describes it as a trip button marked "T" or "Test" (ST, "Garis Panduan Pendawaian Elektrik Pepasangan Domestik", section 11.2.5).
- Tell everyone at home first. The circuits behind the RCD will lose power for a moment, so save any work on a computer.
- Dry your hands and wear rubber slippers. myTNB asks for both when you handle the RCCB (TNB, myTNB "RCCB" page).
- Open the DB box cover and find the RCD. Look for the switch with the small T or Test button.
- Press the button once, firmly. The lever should drop to OFF, and the lights on those circuits go out.
- Push the lever back up to ON. Power should come back on those circuits.
- Note the date. A phone reminder for the same day next month keeps the habit going.
This button test has a limit. ST's guideline says it cannot show how sensitive the RCD is, or how fast it trips. A wireman checks that with an RCD tester when the wiring is tested.
If it does not trip
If nothing happens when you press the test button, treat the RCD as not working. ST's booklet says the next step is a contractor registered with ST, who can inspect, repair or replace it (ST, "Tip Keselamatan dan Kecekapan Tenaga").
Do not take the board apart or swap the unit yourself. Until the contractor comes, be extra careful with appliances near water, such as the water heater. ST's booklet says a water heater should be protected from current leakage by an RCD in the board.
When you ask for quotes, say "RCD does not trip on test" in the job description. That tells the contractor what to bring.
If it keeps tripping on its own
An RCD that trips again and again without you pressing the button is a different problem. myTNB says an RCD that trips when one MCB is switched on can mean a wiring problem on that circuit (TNB, myTNB "RCCB" page).
This page does not cover that fault. For help with a board that keeps cutting out, ask an electrician through the home electrical work page.
Get quotes on Dispatcher
Free for homeowners. Describe the job in one short form and we pass it to matched local contractors, who contact you directly. Have a photo of your DB board ready to send to the matched contractors when they contact you.
Dispatcher does not do the work, and has not checked licences for listed businesses. Ask each firm for its ST registration before work starts. For a new board or rewiring, use the electrical wiring page. There is more on how Dispatcher works and in our other help guides.
Need someone to check it? Read our guide to booking an electrician home visit.
Sources
Sources: these pages were read on the update date above.
Frequently asked questions
What is an RCD?
An RCD is the safety switch in your distribution board that cuts the power when current leaks out of the wiring. RCD means residual current device. In Malay it is the Peranti Arus Baki. Many people call it the RCCB, which is one type of RCD. ST describes it as protection against electric shock.
How often should I test my RCD?
Test it at least once a month. That is the advice in the safety booklet from Suruhanjaya Tenaga, the energy regulator. Press the T or Test button and check that the switch trips. Set a monthly phone reminder so you do not forget the next one.
What should happen when I press the test button?
The RCD should trip straight away. Its lever drops to OFF and the power on the circuits it protects goes off. Push the lever back up to ON to restore power. If the lever does not move at all, the RCD has failed the test and needs a registered electrical contractor.
What if my RCD does not trip when I test it?
Treat it as not working and get an electrical contractor registered with Suruhanjaya Tenaga to inspect, repair or replace it. That is the step the ST safety booklet gives. Do not take the board apart yourself. When you ask for quotes, write that the RCD did not trip on test.
What if the RCD trips on its own?
Tripping on its own is a different problem from a failed test. It can point to a wiring problem on one circuit, and an electrician needs to find the cause. Leave the board alone until then. Note which MCB you had just switched on when it tripped, and tell the contractor.
Next step Test failed, or want the board checked? Get quotes